Duct Fitting Loss Coefficients: entry_rect_ed7_2
Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.
| fitting type | size or range | C0 (dimensionless) | ashrae code | geometry notes | standard |
|---|---|---|---|---|---|
| entry_rect_ed7_2 | Ldo0.5_vr0 | 1.8 | ED7-2 | Rectangular main entry ED7-2; L/Do=0.5, velocity ratio pv_out/pv_in=0; C referenced to upstream duct Vp | ASHRAE Handbook Fundamentals 2021 Ch.21 Table 7 |
| entry_rect_ed7_2 | Ldo0.5_vr10 | 0.53 | ED7-2 | Rectangular main entry ED7-2; L/Do=0.5, velocity ratio=10 | ASHRAE Handbook Fundamentals 2021 Ch.21 Table 7 |
| entry_rect_ed7_2 | Ldo0.5_vr2 | 1 | ED7-2 | Rectangular main entry ED7-2; L/Do=0.5, velocity ratio=2 | ASHRAE Handbook Fundamentals 2021 Ch.21 Table 7 |
This is a sample. Search the full duct fitting loss coefficients dataset and 350+ more by creating a free account and accessing the database.
Get started for FREERelated data
damper_butterfly_50pct_open1 rowdamper_butterfly_fully_open1 rowelbow_45_smooth_r1.01 rowelbow_45_smooth_r1.51 rowelbow_60_3gore_r1.51 rowelbow_90_3gore_r1.51 rowelbow_90_7gore_r2.51 rowelbow_90_mitered_double_vane1 rowelbow_90_mitered_single_vane1 rowelbow_90_mitered_unvaned1 rowelbow_90_rect_smooth_r1.01 rowelbow_90_rect_smooth_r1.51 row