Disconnect Switch Specs: 345KV
Disconnect switch ratings by voltage class and continuous current per IEEE C37.30. Includes momentary withstand, short-time withstand, BIL, switch type, phase spacing, and operating mechanism.
| voltage class | continuous current A | bil kV (kV) | momentary withstand kA crest (kA) | operating mechanism | phase spacing in (in) | short time withstand kA rms (kA) | standard | switch type |
|---|---|---|---|---|---|---|---|---|
| 345KV | 1,200 | 1,300 | 80 | MOTOR | 264 | 31.5 | IEEE C37.30-2011 | GANG_OPERATED_DOUBLE_BREAK |
| 345KV | 2,000 | 1,300 | 105 | MOTOR | 264 | 40 | IEEE C37.30-2011 | GANG_OPERATED_DOUBLE_BREAK |
This is a sample. Search the full disconnect switch specs dataset and 300+ more by creating a free account and accessing the database.