Datacenter Efficiency Metrics: Power Density Parameter

Colocation Peak Power Per Cabinet to Large DC Power Density Pod

Data center efficiency metrics and benchmarks from Green Grid and Schneider Electric whitepapers. Covers PUE measurement levels (L1/L2/L3), source energy weighting factors (global and US), PUE reporting classifications (Unrecognized/Reported/Registered), NCPI component loss percentages (UPS, PDU, CRAC, chiller, wiring), energy reduction strategy savings ranges, power density parameters by data center type (small enterprise, large enterprise, colocation, cloud, HPC), heat output conversion factors and formulas, and DLC (direct liquid cooling) industry documentation references.

Electrical Engineeringmetric category: Power Density Parameter9 rowsPage 2 of 4
metric categoryitem namedescriptionunitvalue numeric (varies by item)
Power Density ParameterColocation Peak Power Per CabinetPeak power per cabinet (highest-power cabinet) for colocationkW12
Power Density ParameterColocation Power UncertaintyUnit power uncertainty for colocationpercent50
Power Density ParameterHPC Ancillary SpaceSpace reserved for ancillary systems in HPCpercent of room5
Power Density ParameterHPC Avg Power Per CabinetDesign target average power per cabinet for HPCkW16
Power Density ParameterHPC Managed Power RatioManaged power ratio for HPCpercent90
Power Density ParameterHPC Peak Power Per CabinetPeak power per cabinet (highest-power cabinet) for HPCkW25
Power Density ParameterHPC Power UncertaintyUnit power uncertainty for HPCpercent50
Power Density ParameterLarge DC Power Density FacilityPower density at facility level for large 2 MW data center exampleW/sqft79
Power Density ParameterLarge DC Power Density PodPower density at pod level for large 2 MW data center exampleW/sqft179