UPS-with-Battery — Heat Output Formula

Metric Category
Heat Output Formula
Item Name
UPS with Battery
Description
Heat Output Formula for UPS with battery; Function of UPS Rated Power and IT Load
Unit
W
Value Text
0.04 * UPS Rating + 0.05 * IT Load
Heat Output Formula — item name UPS_With_Battery · description Heat output formula for UPS with battery; function of UPS rated power and IT… · value text 0.04 * UPS_rating + 0.05 * IT_load · unit W | Datacenter Efficiency Metrics | Engineering Database