Home/Reference Data/Datacenter Cooling Specs/Vertiv_Liebert_DS_105_WC_upflow_FW

Datacenter Cooling Specs: Vertiv_Liebert_DS_105_WC_upflow_FW

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer_model: Vertiv_Liebert_DS_105_WC_upflow_FW3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)entering water temp c (degC)leaving water temp c (degC)manufacturermodel seriessensible cooling capacity kw (kW)total cooling capacity kw (kW)water flow rate lpm (L/min)
Vertiv_Liebert_DS_105_WC_upflow_FWcooling_capacity_75F_DB_EWT83Fupflowsemi_hermeticwater_cooled23.928.335VertivLiebert DS80.394.6272.4
Vertiv_Liebert_DS_105_WC_upflow_FWcooling_capacity_80F_DB_EWT83Fupflowsemi_hermeticwater_cooled26.728.335VertivLiebert DS92.3100.3284.7
Vertiv_Liebert_DS_105_WC_upflow_FWcooling_capacity_85F_DB_EWT83Fupflowsemi_hermeticwater_cooled29.428.335VertivLiebert DS100.9104.9295.8