Datacenter Cooling Specs: Vertiv_Liebert_DS_105_WC_upflow_FW
Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.
| manufacturer model | spec type | airflow direction | compressor type | cooling type | entering air temp c (degC) | entering water temp c (degC) | leaving water temp c (degC) | manufacturer | model series | sensible cooling capacity kw (kW) | total cooling capacity kw (kW) | water flow rate lpm (L/min) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Vertiv_Liebert_DS_105_WC_upflow_FW | cooling_capacity_75F_DB_EWT83F | upflow | semi_hermetic | water_cooled | 23.9 | 28.3 | 35 | Vertiv | Liebert DS | 80.3 | 94.6 | 272.4 |
| Vertiv_Liebert_DS_105_WC_upflow_FW | cooling_capacity_80F_DB_EWT83F | upflow | semi_hermetic | water_cooled | 26.7 | 28.3 | 35 | Vertiv | Liebert DS | 92.3 | 100.3 | 284.7 |
| Vertiv_Liebert_DS_105_WC_upflow_FW | cooling_capacity_85F_DB_EWT83F | upflow | semi_hermetic | water_cooled | 29.4 | 28.3 | 35 | Vertiv | Liebert DS | 100.9 | 104.9 | 295.8 |
This is a sample. Search the full datacenter cooling specs dataset and 350+ more by creating a free account and accessing the database.
Get started for FREERelated data
Schneider_CDU_floor_LA_60kW1 rowSchneider_CDU_rack_LL_40_80kW1 rowSchneider_InRow_RC_600mm_ACRC6002 rowsSchneider_InRow_RP_600mm_ACRC600P2 rowsVertiv_Liebert_CRV_20kW_DX_AC2 rowsVertiv_Liebert_CRV_35kW_DX_AC2 rowsVertiv_Liebert_CRV_CR020RA2 rowsVertiv_Liebert_CRV_CR035RA2 rowsVertiv_Liebert_CRV_CR060RC2 rowsVertiv_Liebert_DS_035_DX_downflow3 rowsVertiv_Liebert_DS_035_Glycol_upflow3 rowsVertiv_Liebert_DS_0422 rows