Cooling-Capacity-80F-Db-EWT104F — Vertiv Liebert Ds 077 Glycol Upflow

Manufacturer Model
Vertiv Liebert Ds 077 Glycol Upflow
Spec Type
Cooling Capacity 80F Db EWT104F
Airflow Direction
Upflow
Compressor Type
Semi Hermetic
Cooling Type
Glycol Cooled
Entering Air Temp C (degC)
26.7
Entering Water Temp C (degC)
40
Leaving Water Temp C (degC)
46.1
Manufacturer
Vertiv
Model Series
Liebert Ds
Sensible Cooling Capacity Kw (kW)
69.7
Total Cooling Capacity Kw (kW)
72
Water Flow Rate Lpm (L/min)
272.8
Vertiv_Liebert_DS_077_Glycol_upflow — spec type cooling_capacity_80F_DB_EWT104F · water flow rate lpm 272.8 L/min · entering air temp c 26.7 degC · sensible cooling capacity kw 69.7 kW · total cooling capacity kw 72 kW | Datacenter Cooling Specs | Engineering Database