Datacenter Cooling Specs: Vertiv_Liebert_DS_070_WC_downflow_FW

Datacenter precision cooling unit specifications — CRAC/CRAH, in-row cooling (chilled water, DX, glycol), and liquid cooling CDUs. Covers Schneider Electric InRow RC/RP and Vertiv Liebert CRV, DS, PCW, XDU, and XDU 1350. Distinct from chiller_performance which covers central plant chillers.

Mechanical Engineeringmanufacturer_model: Vertiv_Liebert_DS_070_WC_downflow_FW3 rows
manufacturer modelspec typeairflow directioncompressor typecooling typeentering air temp c (degC)entering water temp c (degC)leaving water temp c (degC)manufacturermodel seriessensible cooling capacity kw (kW)total cooling capacity kw (kW)water flow rate lpm (L/min)
Vertiv_Liebert_DS_070_WC_downflow_FWcooling_capacity_75F_DB_EWT83Fdownflowsemi_hermeticwater_cooled23.928.335VertivLiebert DS6374.1205.9
Vertiv_Liebert_DS_070_WC_downflow_FWcooling_capacity_80F_DB_EWT83Fdownflowsemi_hermeticwater_cooled26.728.335VertivLiebert DS70.777.3212.9
Vertiv_Liebert_DS_070_WC_downflow_FWcooling_capacity_85F_DB_EWT83Fdownflowsemi_hermeticwater_cooled29.428.335VertivLiebert DS77.780.7220.5