Cooling-Capacity-75F-Db-EWT104F — Vertiv Liebert Ds 035 Glycol Upflow

Manufacturer Model
Vertiv Liebert Ds 035 Glycol Upflow
Spec Type
Cooling Capacity 75F Db EWT104F
Airflow Direction
Upflow
Compressor Type
Digital Scroll
Cooling Type
Glycol Cooled
Entering Air Temp C (degC)
23.9
Entering Water Temp C (degC)
40
Leaving Water Temp C (degC)
46.1
Manufacturer
Vertiv
Model Series
Liebert Ds
Sensible Cooling Capacity Kw (kW)
31.1
Total Cooling Capacity Kw (kW)
32
Water Flow Rate Lpm (L/min)
121.2
Vertiv_Liebert_DS_035_Glycol_upflow — spec type cooling_capacity_75F_DB_EWT104F · water flow rate lpm 121.2 L/min · entering air temp c 23.9 degC · sensible cooling capacity kw 31.1 kW · total cooling capacity kw 32 kW | Datacenter Cooling Specs | Engineering Database