5000:5 to 800:5

CT and VT standard ratios, accuracy classes, burden designations, and IEC/IEEE accuracy limits per IEEE C57.13 and IEEE Std 3004.1-2013. Covers metering CTs, relaying CTs (C-class), standard CT/VT burdens, and IEC accuracy limits.

Electrical Engineeringinstrument transformer type: CT RELAYING4 rowsPage 2 of 2
instrument transformer typeratio designationaccuracy classmechanical short time rating kA (kA)ratio value (dimensionless)standard burden VA (VA)thermal rating factor trf (dimensionless)
CT RELAYING5000:5C800611,0008001.5
CT RELAYING600:5C400401204001.5
CT RELAYING75:5C10040151001.5
CT RELAYING800:5C400401604001.5