Chp System Data: engine_room_ventilation

CHP (combined heat and power) system reference data from ASHRAE 2020 Ch.7 — CHP efficiency metrics, boiler heat recovery factors, grid electrical efficiency references, reciprocating engine sizing, exhaust pipe sizing, gas fuel line pressures, engine room ventilation, maintenance intervals, fuel cell technology comparison, theoretical steam rates, steam turbine governor classes, heat recovery temperature ranges, engine exhaust properties, and engine-driven chiller COP

Mechanical Engineeringparameter_type: engine_room_ventilation3 rows
parameter typeparameter iddescriptionunitvalue text
engine_room_ventilation10f_rise_air_cooledEngine room ventilation — 10°F rise air- or radiator-cooled enginecfm/hp550
engine_room_ventilation10f_rise_muffled_insideEngine room ventilation — 10°F rise muffler/exhaust inside buildingcfm/hp280
engine_room_ventilation10f_rise_muffled_outsideEngine room ventilation — 10°F rise muffler/exhaust outside buildingcfm/hp140