Cable Impedance Data: fieldbus_DeviceNet to triax
Characteristic impedance, attenuation at multiple frequencies, capacitance per foot, velocity of propagation, and signal properties for communication and control cables. Covers coaxial (RG58/RG6/RG11/RG213), twisted pair (Cat5e through Cat8), twinax, instrument cable, thermocouple extension, fiber optic (OS2/OM3/OM4), triaxial, and industrial fieldbus cables (Profibus DP, DeviceNet).
| cable type | attenuation dB per 100ft at 100MHz (dB/100ft) | attenuation dB per 100ft at 10MHz (dB/100ft) | bend radius min in (in) | capacitance pF per ft (pF/ft) | conductor gauge AWG (AWG) | impedance ohms (ohm) | jacket material | max distance ft (ft) | max frequency MHz (MHz) | max pull tension lb (lbf) | notes | shield type | velocity of propagation pct (%c) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| fieldbus_DeviceNet | 6 | 0.4 | 2.5 | 35 | 18 | 121 | PVC | 1,600 | 1 | 100 | DeviceNet thick trunk cable; 18AWG signal pair + 15AWG power pair + drain; 120Ω nominal (121Ω termination); max trunk length 500m at 125kbps; 200m at 250kbps; 100m at 500kbps (1600ft at 125kbps); per ODVA DeviceNet Media Design Guide | braid_foil | 67 |