Ap42 Emission Factors: wood_combustion_boiler

EPA AP-42 Fifth Edition air pollutant emission factors for stationary combustion and area sources — uncontrolled emission factors in lb/MMBtu (combustion) or lb/hp-hr (engines) or lb/VMT (roads) for NOx, CO, SO2, PM10, PM2.5, VOC. Covers natural gas boilers (small <100 MMBtu/hr, large wall-fired >100 MMBtu/hr, large tangential >100 MMBtu/hr), diesel engines (4-stroke, 2-stroke stationary), gasoline engines (4-stroke), bituminous coal (pulverized and stoker), No. 2 distillate and No. 6 residual fuel oil, wood combustion boilers, LPG boilers, fugitive dust (construction, unpaved roads, material handling), and painting/coating VOC. Sources: EPA AP-42 5th Ed. Chapters 1.1, 1.3, 1.4, 1.5, 1.6, 3.3, 4.2, 13.2.2, 13.2.4; EPA WebFIRE database; 40 CFR Part 51 Appendix S.

Mechanical Engineeringsource_category: wood_combustion_boiler3 rows
source categoryrecord idap42 sectionap42 tableef ratingemission factornotespollutantscc codeunit
wood_combustion_boilerwood_boiler_CO1.61.6-1C0.3Wood boiler CO uncontrolled; high due to wet fuel variabilityCO1-02-009-01lb/MMBtu
wood_combustion_boilerwood_boiler_NOx1.61.6-1C0.17Uncontrolled wood-fired boiler (bark/wood waste/slash); industrial spreader stokerNOx1-02-009-01lb/MMBtu
wood_combustion_boilerwood_boiler_PM101.61.6-1C0.41Uncontrolled wood boiler PM10; high due to fly ash and charPM101-02-009-01lb/MMBtu

This is a sample. Search the full ap42 emission factors dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE

Related data